A) Excessive pitting and welding of contacts chattering is caused by following reason
1) Reasons: Coil not picking due to low voltage
Remedy: Ensure correct voltage conditions In case of persistent low voltage change coil to lower voltage or change control transformer tapping
2) Reason: Broken Short circuit ring (Shading ring)
Remedy: The mechanical life of contactor is over. Replace the contactor
3)Chattering in switching device
Remedy: Check & correct the condition in the control circuit
4)Reason: Small cross section/long length
Remedy: Select sizes as per guideline in sect on of control cable control wiring
5)Reason: Improper termination of control cable
Remedy: Use proper lugs for termination
6)Inadequate capacity of control transformer
Remedy: Use correct control transformer
7)Reason: Capacitor switching
Remedy: Use correct contactor & follow guidelines
8)Reason: Short circuit during star delta changeover
Remedy: – Use 7PU 60 20 timer
9)Reason: Reversing application (cranes)
Remedy: Use interlocked contactors with electrical interlocking
........