• Twist the connecting leads while measuring to avoid false pick ups
• Measure current with clip on meter
• The values of drop measured should be less than 4.0mV at the rated current of contactor for AC3 duty. mV volt drop can be calculated by given formula:

Milivolt drop test
Corrective action: If milivolt drop is more, then it is indication of bad joints
For case A & B) Clean the surfaces, apply Dowells crimping compound & re-crimp cables

Image A

Image b
For case C) Higher value of mV drop in this case could be due to either case A or B; In case of persistent higher value, replacement of the entire contactor is necessary

Image C
........